Skip to Content
Low Voltage Switchgear

China Low Voltage Switchgear Cabinet Factory

Custom low voltage switchgear, switchboards, MDB, MCC, ATS, APFC and LV distribution panels, built around your SLD, panel schedule, load list and site installation requirements.

You can send your single-line diagram, circuit list or project specification. Your engineering team confirms rated current, short-circuit level, busbar design, breaker configuration, cable entry, control logic, drawings, FAT and project documents before production.

IEC 61439 LV Assemblies
MDB / MCC / ATS / APFC
ACB / MCCB Configuration
FAT & Project Documents
Low voltage switchgear cabinets on the ZOE production line
Low voltage switchgear cabinet MDB main distribution board MCC motor control center Busbar system inside LV panel
ATS automatic transfer switch panel APFC power factor correction panel ACB air circuit breaker Cable entry section of switchgear
What We Build

LV Switchgear Built Around Your Project

Send your single-line diagram, load schedule, panel schedule or project specification. We build LV switchgear, MDB, MCC, PCC, ATS, APFC and distribution panels that match your exact electrical configuration and site conditions.

Every Panel Built To Your

Rated Current & Short-circuit Level
Breaker Configuration & Busbar System
Cable Entry Direction & IP Rating
Form Of Separation & Control Voltage
Metering & Communication
Applicable Standards

Drawings, BOM, test reports, FAT records and project documents are prepared for your approval and delivery.

Factory Capabilities

Low Voltage Switchgear Manufactured In Our China Factory

Your LV switchgear project may need more than a standard distribution panel. We manufacture project-based assemblies around your SLD, load schedule, circuit list, rated current, fault level, breaker configuration, busbar system, cable entry direction, control logic and document requirements.

Engineer reviewing a single-line diagram

SLD-Based Engineering

We review your single-line diagram, load schedule and feeder list before panel layout and quotation.

Project low voltage assemblies on the production line

Project LV Assemblies

MDB, MCC, PCC, ATS, APFC and distribution panels built for building, industrial and EPC projects.

Circuit breakers installed inside a switchgear panel

Breaker Configuration

ACB, MCCB, MCB, contactor, soft starter and VFD options selected according to your load and protection needs.

Copper busbar system inside a low voltage cabinet

Busbar & Cable Space

Busbar rating, short-circuit level, neutral and PE busbar and cable entry direction are checked during design.

Secondary wiring and control terminals

Control & Communication

Secondary wiring, metering, ATS logic, MCC control, APFC control and communication terminals prepared as required.

GA drawings and project documents

Documents For Approval

GA drawings, schematic diagrams, BOM, wiring diagrams, test reports, FAT records and O&M documents can be supplied.

Engineering First

Not Sure Which LV Configuration Your Project Needs?

Send your single-line diagram, load schedule or circuit list. Our engineering team checks rated current, fault level, breaker selection and busbar design with you before any quotation, so you order the right panel the first time.

Product Range

Low Voltage Switchgear Cabinets We Manufacture

We manufacture LV switchgear cabinets for power distribution, motor control, power transfer, power factor correction and project-specific control. Each panel is configured around your SLD, load schedule, circuit list, rated current, short-circuit level, component preference, cable entry direction and site installation requirements.

Main distribution board for transformer low voltage side
MDB

Main Distribution Board

Main distribution boards for transformer low-voltage side distribution in commercial buildings, industrial plants, data centers and infrastructure projects. Configurations can include main incomer ACB, outgoing MCCB feeders, metering, busbar system, form of separation and top or bottom cable entry.

Project Applications

Low Voltage Switchgear Solutions For Different Projects

LV switchgear is not designed the same way for every project. A commercial building, factory, hospital, data center or renewable site needs different feeder arrangements, protection logic, cable entry, metering and documents. We configure each cabinet around your electrical system, installation space and operation requirements.

LV switchgear for commercial building distribution Commercial Buildings

Commercial Buildings

Designed for main distribution, sub-main distribution, lighting, HVAC, elevators, fire systems and tenant power supply. We support MDB, SMDB, DB and ATS panels with clear circuit arrangement, metering, cable entry design and documents for consultant approval.

LV switchgear for industrial plant power distribution Industrial Plants

Industrial Plants

Stable power distribution for production lines, motors, pumps, compressors and process equipment. We manufacture MCC, PCC, APFC and distribution panels with motor starters, VFD feeders, breaker protection, spare circuits and maintenance-friendly wiring layout.

LV distribution for data center power systems Data Centers

Data Centers

Reliable distribution, clear feeder separation, monitoring and coordination with UPS, generator and PDU systems. We configure LV switchboards, ATS panels and distribution panels with metering, communication terminals, breaker coordination and FAT support before delivery.

Emergency power distribution for hospital projects Hospitals

Hospitals

Essential loads, emergency power supply, medical areas, fire systems and backup generator distribution. We provide ATS panels, MDB, SMDB and emergency distribution panels with clear load separation, transfer logic, status indication, testing records and project documents.

LV AC distribution for renewable energy and BESS Renewable & BESS

Renewable Energy And BESS

LV AC distribution, PCS feeder panels, combiner panels, metering, communication and ventilation design. We build LV panels according to inverter output, fault level, cable entry, protection requirements and site installation conditions.

Durable LV switchgear for infrastructure and utilities Infrastructure

Infrastructure And Utilities

Water treatment, pump stations, transportation facilities and public utilities need durable LV switchgear for long operating cycles. We support MDB, MCC, pump control panels, ATS panels and control cabinets with clear wiring, protection, control logic and maintenance access.

LV switchgear documents for EPC and MEP projects EPC & MEP

EPC And MEP Projects

Accurate drawings, approved component lists, panel schedules, wiring diagrams, FAT records and complete handover documents. We work from your SLD, specification and project requirements to prepare LV switchgear suitable for approval, installation and commissioning.

01 / 07
Project-Based Configuration

Tell Us About Your Project, We Configure The Panel Around It

Whether it is a commercial building, factory, data center, hospital or renewable site, send us your load list and site conditions. We match feeder arrangement, protection, cable entry and documents to your exact application before quotation.

Ratings & Standards

Designed According To Project Ratings And Applicable Standards

Each cabinet should match the electrical ratings, installation environment and standard requirements of your project. Before production, we review your SLD, specification and panel schedule to confirm the main electrical parameters, protection level, cable entry, panel structure and document requirements.

Low voltage switchgear ratings and standards we confirm before production
Item What We Confirm Project Notes
Rated Operational VoltageMain operating voltage of the LV systemCommonly based on project SLD and local grid system
Rated Insulation VoltageInsulation level for the assemblyConfirmed according to switchgear design and component selection
Rated Impulse Withstand VoltageSurge withstand requirementReviewed according to project standard and system condition
Rated FrequencySystem frequency50Hz or 60Hz according to project location
Rated CurrentMain incomer and feeder current ratingsBased on load schedule, transformer capacity and feeder list
Short-time Withstand CurrentBusbar and assembly short-time withstand levelChecked against project fault level
Peak Withstand CurrentPeak short-circuit withstand requirementConfirmed together with short-time withstand rating
Breaker Breaking CapacityACB, MCCB or MCB interrupting capacitySelected according to short-circuit current
Main Busbar RatingMain busbar current capacityDesigned according to rated current and temperature rise consideration
Neutral Busbar RatingNeutral busbar capacityConfirmed according to load type and project requirement
PE BusbarProtective earth busbar designIncluded according to grounding and safety requirements
Form of SeparationInternal separation arrangementForm 1, Form 2, Form 3 or Form 4 can be discussed by project
IP Protection DegreeEnclosure protection levelSelected according to indoor, outdoor, dust or moisture conditions
Installation TypeIndoor or outdoor installationEnclosure, ventilation and protection design are adjusted accordingly
Ambient TemperatureSite operating temperatureUsed for component selection, ventilation and derating review
AltitudeInstallation altitudeConsidered when insulation and temperature rise may be affected
Control VoltageSecondary control circuit voltageAC or DC control voltage according to project design
Cable Entry DirectionTop or bottom cable entryConfirmed before panel layout and fabrication
Access TypeFront access or rear accessDesigned according to room layout and maintenance space
Applicable StandardRequired project standardIEC 61439 or project-specific standard can be followed when applicable

Swipe the table sideways to see all columns.

Get The Ratings Right

Send Your Ratings, We Confirm The Full Specification

Share your rated voltage, current, fault level and standard. We check every parameter against your SLD and load schedule, then return a confirmed spec sheet before you commit to production.

Rated Current
Fault Level
Busbar Rating
Form Separation
IP Degree
IEC 61439
Engineering Support

Engineering Support For LV Panel Design And Drawings

LV switchgear projects depend on accurate drawings before production. Panel size, feeder arrangement, cable entry, breaker configuration, control wiring and terminal layout should be confirmed clearly before the cabinet is built. Our engineering team reviews your SLD, panel schedule, load list, MCC schedule, room layout and specification, then prepares practical drawings and documents for approval, production, installation and FAT.

Step 01

From Project Drawings To Panel Design

We check the electrical system, panel quantity, incoming and outgoing feeders, rated current, fault level, breaker selection, cable direction and installation space before preparing the panel layout.

SLD ReviewFeeder CheckPanel Layout
Step 02

Drawing Support Before Production

We prepare general arrangement drawings, internal layout drawings, foundation drawings, schematic diagrams, control wiring diagrams, terminal plans and cable entry drawings according to your project requirement.

GA DrawingsSchematicsTerminal Plans
Step 03

Fewer Site Installation Problems

Clear drawings help reduce problems such as wrong panel dimensions, incorrect cable entry, unclear feeder numbers, missing terminals, mismatched breaker configuration and incomplete control logic.

Correct DimensionsCable EntryClear Feeders
Step 04

Easier Review And Approval

For EPC, MEP and consultant-reviewed projects, we provide BOM, component list, datasheets, technical deviation sheet, compliance statement, test reports, FAT records and O&M documents when required.

BOM & DatasheetsComplianceFAT Records
1 / 4
Engineering Engineer preparing LV panel layout from project drawings General arrangement and schematic drawings for switchgear Cable entry and installation detail check Document review and approval for EPC projects
From Project Drawings To Panel Design
Protection Coordination

Protection Coordination And Short-circuit Rating Review

A cabinet should not only match the required current rating. It also needs proper short-circuit withstand capacity, breaker breaking capacity and reasonable coordination between the incoming breaker, busbar system and outgoing feeders. We review your SLD, transformer capacity, fault level, load schedule and feeder list to confirm whether the selected ACB, MCCB, MCB, busbar and protection devices suit your electrical system.

Simplified LV Single-line Diagram
Transformer MV / LV step-down Main ACB Incoming breaker BUSBAR SYSTEM MCCB MCCB MCCB DB MCC Load Fault level checked here

Each breaking point and busbar rating is checked against your project fault level.

Fault Level Confirmation

We check the available short-circuit current at the LV side from your project data, transformer capacity and system condition before selecting breakers and busbar ratings.

Breaker Breaking Capacity

ACB, MCCB and MCB breaking capacity is selected according to the fault level at each panel position, not only by load current.

Busbar Withstand Rating

Main busbar, neutral busbar and PE busbar are reviewed against rated current, short-time withstand current and peak withstand current.

Upstream And Downstream Review

We review the relationship between incoming breakers, outgoing feeders and downstream panels to reduce unnecessary power interruption from poor protection arrangement.

Motor And Feeder Protection

For MCC and industrial panels, motor feeders, VFD feeders, soft starters and large loads are reviewed by starting method, protection requirement and control logic.

Protection Setting Support

When project data is available, we support discussion on breaker settings, overload, short-circuit, earth fault protection and selective coordination requirements.

Right Breaker, Right Rating

Worried Your Breaker Rating Might Not Match The Fault Level?

Send your transformer capacity, fault level and feeder list. We check breaking capacity, busbar withstand and protection coordination against your system, so the panel is safe before it goes into production.

Busbar & Ventilation

Busbar Design, Temperature Rise And Ventilation

The busbar system is one of the most important parts of an LV switchgear cabinet. For high-current panels, busbar size, joint connection, support spacing, insulation clearance, ventilation and enclosure protection are reviewed together before production. We design the arrangement around your rated current, short-circuit level, panel structure, ambient temperature, IP rating, cable entry and installation space, for stable current distribution, easier maintenance and better heat dissipation.

Main Busbar Arrangement

Designed around your rated current, incoming feeder position, outgoing feeder arrangement and panel layout. Copper or aluminum busbar can be discussed by project requirement, budget and specification.

Short-circuit Withstand Review

Busbar support, phase spacing and connection structure should match your short-time withstand and peak withstand current. Reviewed together with breaker selection and project fault level.

Joint Connection And Inspection

Busbar joints, contact surfaces, bolts and connection points need careful assembly and inspection. Proper tightening, contact area and clear phase identification help reduce overheating risk.

Temperature Rise And Ventilation

Ventilation is considered together with rated current, enclosure size, IP degree, ambient temperature and component heat loss. Natural ventilation, forced ventilation or layout adjustment can be discussed when required.

Component Options

Component Options Selected Around Your Project

Each LV panel is built with components chosen for your load, protection scheme and project specification. We select breakers, starters, protection devices, metering, control and communication parts according to your rated current, fault level and control requirements.

Air circuit breakers and molded case circuit breakers in a panel
01 / 08 · Breakers

Circuit Breakers

ACB, MCCB, MCB and RCBO are selected by rated current, breaking capacity and protection needs. Branded or project-specified breakers can be supplied according to your requirement and budget.

Discuss Components
Contactors and motor starters inside an MCC panel
02 / 08 · Motor Control

Contactors And Starters

Contactors, overload relays, DOL and star-delta starters, soft starters and VFD feeders are configured by motor rating, starting method and control logic for MCC and industrial panels.

Discuss Components
Protection relays mounted on a switchgear panel door
03 / 08 · Protection

Protection Relays

Overload, short-circuit, earth fault and multifunction protection relays are selected to your protection scheme, feeder type and coordination requirement, with alarm and trip signals as needed.

Discuss Components
Current transformers and meters in a switchgear panel
04 / 08 · Metering

CT, PT And Metering

Current transformers, potential transformers, multifunction meters, ammeters and voltmeters are selected by CT ratio, class and metering points to support accurate measurement and monitoring.

Discuss Components
Control switches, indicators and pilot devices on a panel
05 / 08 · Control

Control And Indication Devices

Control switches, push buttons, selector switches, signal lamps, live voltage indicators and auxiliary contacts are arranged by your local or remote control and indication requirements.

Discuss Components
Insulated busbar and supports inside a low voltage cabinet
06 / 08 · Busbar

Busbar And Insulation

Copper or aluminum busbar, busbar supports, insulators, heat-shrink sleeving and phase barriers are selected by rated current, short-circuit withstand and insulation clearance.

Discuss Components
Terminal blocks and control wiring in a panel
07 / 08 · Wiring

Terminals And Wiring

Terminal blocks, control wiring, cable ducts, ferrules, labels and earthing terminals are prepared to your terminal plan and wiring diagram for clear, maintainable connections.

Discuss Components
Communication modules and monitoring devices in a panel
08 / 08 · Communication

Communication And Monitoring

Communication modules, power meters with Modbus, gateways and monitoring interfaces can be added when your project needs remote metering, status monitoring or integration with a BMS or SCADA system.

Discuss Components
Component Options

Main Components And Configuration Options

LV switchgear performance depends not only on cabinet structure, but also on correct component selection. ACB, MCCB, MCB, contactors, ATS, APFC devices, meters, control relays, PLC, HMI and terminals should match your load type, fault level, control logic, maintenance preference and project specification, with selection guided by spec, local maintenance preference, spare parts availability and budget.

Breakers And Protection Devices

We configure ACB, MCCB, MCB, RCBO, RCD, surge protection devices, current transformers, protection relays and accessories according to rated current, breaking capacity, feeder type and protection requirements.

ACB / MCCBRCBO / RCDSPDRelays

Power Control Components

For MCC, PCC and industrial panels, we configure contactors, thermal overload relays, soft starters, VFDs, motor protection devices, selector switches, indicator lamps and control relays according to motor type and control method.

ContactorsSoft StarterVFDOverload

ATS And APFC Components

ATS panels can use transfer switches, controllers, interlocks and status signals. APFC panels can include APFC controllers, capacitors, contactors, fuses, detuned reactors, ventilation and protection devices for power factor correction.

Transfer SwitchCapacitorsReactorsController

Metering And Communication

Multifunction meters, voltage meters, ammeters, communication modules, PLC, HMI, RS485 terminals, Ethernet interfaces and signal terminals can be prepared for monitoring, local or remote control, or BMS and SCADA connection when required.

MetersPLC / HMIRS485SCADA

Wiring And Terminal System

Terminal blocks, cable lugs, wire markers, ferrules, trunking, grounding connections and clear circuit labels are arranged according to the approved drawings to support installation, testing and maintenance.

TerminalsFerrulesTrunkingLabeling

Swipe sideways to see more categories.

Component Brands
Schneider Electric
ABB
Siemens
Eaton
Chint
LS Electric
Mitsubishi Electric
Schurter
Control & Metering

Control, Metering And Communication Options

For many projects, power distribution is only one part of the requirement. Your panel may also need local control, remote signals, metering, alarm output, communication terminals, ATS logic, MCC motor feedback or APFC control. We prepare the secondary circuit design around your control schematic, SLD, specification and site operation, and test it during FAT when required.

Control, metering and communication devices on a low voltage panel door
Secondary Circuit Design Control wiring, metering and communication confirmed before production.
Local And Remote Control

Panels can be configured for local operation, remote control, selector switches, push buttons, indication lamps, trip signals and alarm contacts according to the operation method your project requires.

Metering And Energy Monitoring

Multifunction meters, current meters, voltage meters, CTs, energy meters and monitoring points can be arranged for incoming feeders, outgoing circuits or key loads according to your panel schedule.

ATS Control Logic

ATS panels can include automatic and manual operation, utility-generator transfer, dual-power transfer, controller settings, interlock logic, status indication and signal terminals for external monitoring.

MCC Motor Feedback

MCC panels can provide motor running status, trip alarm, local and remote control, starter control, VFD control, soft starter control and terminal wiring for field signals.

APFC Control

APFC panels can include power factor controllers, capacitor step control, contactors, fuses, detuned reactors, ventilation control and operation indication according to the compensation requirement.

Communication Interface

When required, RS485, Modbus RTU, Modbus TCP, Ethernet terminals, PLC interface, HMI interface or BMS and SCADA signal points can be prepared according to your project communication requirement.

Manufacturing Process

Low Voltage Switchgear Manufacturing Process

A clear manufacturing process helps reduce drawing mistakes, component mismatch, wiring errors and site installation problems. From project review to FAT and packing, each cabinet is produced according to your approved drawings, BOM, electrical configuration and project requirements.

Project specification review for LV switchgear 01
Project Review

Project Specification Review

We review the project specification, required standards, electrical ratings, installation environment, document requirements and special notes before preparing the technical proposal.

SLD and panel schedule review 02
Engineering

SLD And Panel Schedule Review

The single-line diagram, load schedule, panel schedule, feeder list and MCC schedule are checked to confirm panel quantity, circuit arrangement and main electrical configuration.

Drawing confirmation before production 03
Engineering

Drawing Confirmation

GA drawings, internal layout, schematic diagrams, cable entry drawings, foundation details and BOM are prepared and confirmed before production starts.

Sheet metal fabrication of cabinet frames 04
Fabrication

Sheet Metal Fabrication

Cabinet frames, doors, panels, compartments, cable sections and mounting plates are fabricated according to approved dimensions and structural requirements.

Surface treatment and painting of sheet metal 05
Fabrication

Surface Treatment And Painting

Sheet metal parts are treated and painted according to project requirements, installation environment, enclosure protection and appearance specifications.

Busbar processing for LV switchgear 06
Assembly

Busbar Processing

Main busbar, neutral busbar and PE busbar are processed, arranged and supported according to rated current, short-circuit level and panel structure.

Component installation in switchgear panel 07
Assembly

Component Installation

ACB, MCCB, MCB, contactors, meters, ATS, APFC devices, control parts and terminals are installed according to the approved BOM and layout drawing.

Secondary wiring of control circuits 08
Wiring

Secondary Wiring

Control wiring, metering wiring, ATS logic, MCC control circuits, APFC control and communication terminals are wired according to the schematic diagram.

Labeling and identification of circuits 09
Wiring

Labeling And Identification

Circuit labels, wire markers, terminal numbers, device tags, warning signs and nameplates are prepared for easier installation, operation and maintenance.

Mechanical inspection of cabinet 10
Inspection

Mechanical Inspection

Door operation, locks, interlocks, mounting parts, busbar supports, component installation, cable space and panel dimensions are inspected before electrical testing.

Electrical testing of switchgear 11
Testing

Electrical Testing

Insulation, continuity, wiring, control functions, breaker operation, metering, ATS transfer logic, MCC functions and APFC operation are tested when applicable.

FAT and packing of finished cabinets 12
Delivery

FAT And Packing

FAT records, inspection documents and final confirmation can be prepared before packing. Panels are packed according to shipment method and project delivery requirements.

01 / 12
From Drawing To Delivery

Want A Quote That Matches Your Exact Panel Build?

Send your SLD, panel schedule and specification. We confirm the configuration, drawings and documents before production, so the quote and the delivered cabinets match what your project actually needs.

Quality Control

Quality Control For Low Voltage Switchgear Cabinets

Each cabinet is checked against your approved drawings, BOM and project requirements before delivery. Inspection focuses on component matching, busbar assembly, wiring accuracy, circuit labeling, mechanical operation and electrical functions to reduce avoidable problems during installation and commissioning.

Component inspection against approved BOM 01Component

Component Inspection

Incoming components are checked against the approved BOM, including breaker model, current rating, accessories, meters, control devices and terminal parts.

Busbar arrangement and joint inspection 02Busbar

Busbar Inspection

Main busbar, neutral busbar and PE busbar are checked for arrangement, support, phase clearance, joint connection and clear identification.

Secondary wiring inspection against schematic 03Wiring

Wiring Inspection

Secondary wiring is checked against the schematic diagram, terminal plan, control logic, wire markers and circuit numbers.

Labeling and identification check before packing 04Labeling

Labeling Check

Device labels, feeder names, terminal numbers, warning signs, nameplates and circuit identification are checked before packing.

Mechanical operation and interlock check 05Mechanical

Mechanical Check

Doors, locks, hinges, interlocks, mounting plates, breaker operation, drawer movement and cable space are inspected before testing.

Electrical function testing of the cabinet 06Electrical

Electrical Function Check

Insulation, continuity, breaker operation, metering, ATS logic, MCC control, APFC operation and signal feedback are tested when applicable.

Checked Before It Ships

Every Cabinet Inspected Against Your Approved Drawings

Component matching, busbar assembly, wiring, labeling, mechanical operation and electrical functions are all checked before delivery. Ask for inspection records, test reports and FAT so you see the results before the panels leave the factory.

Factory Testing

Factory Testing And FAT Before Delivery

Before delivery, each cabinet can be inspected and tested according to your approved drawings, BOM, project specification and applicable test requirements. FAT documents and test records can be prepared when required.

FAT Process

A Test Sheet You Can Review And Sign Off

Routine tests, function checks and inspection records can be completed and documented before shipment. You can request the full test sheet, FAT report and witness, third-party or remote FAT when your project needs it.

Tested to your drawings against the approved BOM and specification.

Documented results with test records and a full FAT report.

Witness FAT available on site, by third party or remotely.

Factory Acceptance Test — Item List 16 Items
  • Visual Inspection
  • Dimension Check
  • Wiring Continuity Check
  • Insulation Resistance Test
  • Dielectric Withstand Test
  • Main Circuit Connection Check
  • Secondary Circuit Function Test
  • Mechanical Operation Test
  • Breaker Operation Check
  • ATS Transfer Logic Test
  • MCC Control Function Test
  • APFC Step Operation Test
  • Meter And Signal Check
  • Protection Setting Check If Required
  • Labeling And Nameplate Check
  • FAT Report
Risk Reduction

How We Help Reduce Procurement And Commissioning Risks

LV switchgear problems often come from unclear circuit configuration, wrong breaker selection, poor cable entry planning, incomplete drawings or missing function tests. We review the project information before production to reduce avoidable risks during approval, installation, testing and commissioning.

Wrong Circuit Configuration

We review your SLD, load schedule, panel schedule and feeder list before preparing the panel layout and BOM.

Insufficient Short-circuit Rating

We check fault level, breaker breaking capacity and busbar withstand requirement according to your project data.

Poor Protection Coordination

Incoming breakers, outgoing feeders and downstream panels are reviewed to reduce unnecessary power interruption.

Busbar Overheating Risk

Busbar size, joint connection, support, ventilation and enclosure design are checked against rated current and site conditions.

Cable Entry Problems

Top or bottom cable entry, cable compartment, gland plate and bending space are confirmed before fabrication.

Control Wiring Errors

ATS logic, MCC control, APFC control, metering signals and terminal wiring are checked against approved schematics.

Component Maintenance Difficulty

Component brands are selected by project specification, spare parts availability and maintenance preference.

Approval Document Delays

GA drawings, schematics, BOM, datasheets, test reports, FAT records and O&M documents are prepared when required.

8 Checks

reviewed before production to cut procurement, installation and commissioning risks on your project.

Catch Problems Early

Let Us Review Your Project Before You Order

Send your SLD, load schedule and specification. We check circuit configuration, breaker selection, busbar, cable entry, control wiring and documents, so issues are found on paper and not on site.

Project Documents

Engineering Documents For Project Approval

Your project often needs clear documents for consultant review, EPC submittal, production confirmation, FAT and final handover. We prepare them according to your specification, approved drawings and delivery requirements.

Proposal Stage

Proposal Documents

  • Technical Datasheet
  • Commercial Quotation
  • SLD Review & Panel Schedule
  • Compliance & Deviation Sheet

Approval Stage

Approval Drawings

  • GA & Internal Layout
  • Foundation & Cable Entry
  • Schematic Diagram
  • Control Wiring & Terminal Plan

Design Stage

Electrical & Component Lists

  • BOM & Component List
  • Breaker & CT List
  • Metering List
  • APFC Config & ATS Logic

Handover Stage

Test & Handover Documents

  • Routine Test & FAT Report
  • O&M Manuals
  • Packing List
  • Quality & Origin Certificates
Project Cases

Low Voltage Switchgear Project Experience

Different projects need different LV configurations. Below are typical applications where MDB, MCC, ATS, APFC, LV switchboards and distribution panels are designed around your SLD, load schedule, installation space, control logic and document requirements.

MDB panels for a commercial buildingMDB · Commercial Building

MDB Panels For Commercial Building

Application

Office building, shopping mall or mixed-use building power distribution.

Challenge

Many outgoing feeders, limited electrical room space, strict drawing review and clear circuit identification.

Our Support

MDB layout with main incomer, outgoing MCCB feeders, metering, bottom or top cable entry, GA drawing, BOM and test report.

MCC panels for an industrial plantMCC · Industrial Plant

MCC Panels For Industrial Plant

Application

Manufacturing plant, production line, pump system or motor control area.

Challenge

Multiple motors, mixed starting methods, field signals and maintenance access requirements.

Our Support

MCC panels with DOL starters, star-delta starters, soft starters, VFD feeders, terminal plans, control wiring and function testing.

ATS panel for emergency powerATS · Emergency Power

ATS Panel For Emergency Power

Application

Hospital, data center, commercial building or emergency power distribution system.

Challenge

Utility-generator transfer, dual-power supply, interlock logic, status feedback and transfer reliability.

Our Support

ATS panel with controller, automatic and manual operation, mechanical and electrical interlock, signal terminals and FAT simulation.

APFC panel for a factoryAPFC · Factory

APFC Panel For Factory

Application

Factory, workshop, hotel, commercial facility or site with large inductive loads.

Challenge

Low power factor, capacitor step control, harmonic condition, ventilation and protection requirements.

Our Support

APFC panel with controller, capacitor steps, contactors, fuses, detuned reactor option, metering and operation test.

LV switchboards for a data centerSwitchboard · Data Center

LV Switchboards For Data Center

Application

Data center power room, UPS system, generator distribution or critical load distribution.

Challenge

High reliability, feeder separation, metering, monitoring, short-circuit rating and FAT requirements.

Our Support

LV switchboards with ACB and MCCB configuration, busbar system, metering, communication terminals, clear feeder arrangement and FAT records.

LV panels for renewable energy and BESSLV · Renewable & BESS

LV Panels For Renewable Energy And BESS

Application

Solar plant, BESS container, PCS feeder, AC combiner or renewable energy distribution system.

Challenge

Inverter output connection, multiple feeders, metering, communication, cable entry and ventilation requirements.

Our Support

LV distribution panels with feeder protection, metering, signal terminals, cable entry design, ventilation review and project documents.

01 / 06
Buying Process

How To Buy Low Voltage Switchgear From Our Factory

Buying LV switchgear should start with technical confirmation, not only price comparison. We review your drawings, circuit list, ratings, cable entry, component requirements and documents before production, so the final panels match your project design and site installation needs.

Low voltage switchgear production and FAT at the factory
From Drawing To Delivery Technical confirmation first, so your panels match the project. Start Your Inquiry

Send Project Information

Send your SLD, load schedule, panel schedule, circuit list, project specification or room layout.

Engineering Review

We review the electrical system, panel quantity, feeder arrangement, rated current, fault level and installation conditions.

Confirm Panel Configuration

Panel type, incoming feeders, outgoing circuits, breaker configuration, busbar rating, cable entry and control requirements are confirmed.

Technical And Commercial Proposal

We prepare the LV switchgear proposal according to the confirmed electrical configuration and project requirements.

Drawing And BOM Approval

GA drawings, schematic diagrams, cable entry drawings, terminal plans and BOM are confirmed before production.

Production And Assembly

Cabinet fabrication, busbar processing, component installation, secondary wiring and labeling are completed to approved drawings.

Factory Testing And FAT

Mechanical checks, electrical tests, secondary function tests, ATS logic, MCC control and APFC operation tests are carried out when applicable.

Packing And Shipment

Panels are packed according to shipment method, cabinet size, accessories and project delivery requirements.

Installation Documents And Support

Test records, drawings, packing list, operation manual, maintenance documents and other required files can be prepared for installation and handover.

FAQ

FAQ About Low Voltage Switchgear Cabinets

Common questions on configuration, breaker selection, busbar design, separation, testing and project documents. If your question is not covered here, send your drawings and we will review it with you.

What information is needed to configure a low voltage switchgear cabinet?

Send your single-line diagram, panel schedule, load schedule, feeder list or project specification. Important details include rated voltage, rated current, transformer capacity, fault level, incoming breaker type, outgoing circuits, cable entry direction, IP rating, form of separation, control voltage, metering, communication and required documents. These inputs help confirm panel type, breaker configuration, busbar rating, internal layout and the technical proposal.

Can LV switchgear be manufactured according to my project SLD?

Yes. LV switchgear can be configured according to your single-line diagram, load schedule and circuit list. The SLD helps confirm the main incomer, outgoing feeders, busbar arrangement, protection devices, metering points, ATS requirements, APFC requirements and downstream panel connections. Before production, drawings and BOM should be reviewed so the cabinet design matches the project electrical system.

How do you select ACB, MCCB and MCB ratings?

Breaker selection is based on load current, fault level, breaking capacity, protection requirement, feeder type and coordination with upstream and downstream devices. ACBs are commonly used for main incomers or large feeders, while MCCBs and MCBs are used for outgoing circuits and smaller loads. The final selection is confirmed according to project specification, short-circuit current and approved component brand requirements.

How is the busbar system designed for an LV switchgear cabinet?

The busbar system is designed according to rated current, short-circuit withstand requirement, panel structure, feeder arrangement, ambient temperature and installation condition. Main busbar, neutral busbar and PE busbar are reviewed together with breaker selection and cable entry. Busbar material, size, support, phase clearance, joint connection and ventilation are important points for stable operation and temperature rise control.

Can you support Form 2, Form 3 or Form 4 separation?

Form of separation can be discussed according to project specification and maintenance requirements. Different separation forms affect the arrangement of busbars, functional units, terminals and cable compartments. For MDB, MCC, PCC and main LV switchboards, internal separation should be confirmed before panel design because it affects cabinet size, accessibility, wiring space, component layout and future maintenance.

Can the cabinet structure match my electrical room layout?

Yes. Panel dimensions, front or rear access, top or bottom cable entry, plinth height, gland plate, cable compartment, door opening direction and maintenance clearance can be reviewed according to your room layout. This confirmation is important before production, because incorrect cable entry or insufficient maintenance space can cause installation problems at site.

Can ATS, MCC and APFC functions be integrated into the LV panel system?

Yes. ATS, MCC and APFC panels can be configured according to your project requirement. ATS systems may include transfer controller, automatic and manual operation, interlock and status signals. MCC panels may include DOL starters, star-delta starters, soft starters or VFD feeders. APFC panels may include power factor controller, capacitor steps, contactors, fuses, detuned reactors and ventilation design.

Can metering, communication and remote signals be added?

Yes. LV switchgear can include multifunction meters, CTs, voltage meters, energy meters, alarm contacts, trip signals, status feedback, RS485 terminals, Modbus communication, Ethernet interface, PLC interface or BMS and SCADA signal points when required. These functions should be confirmed during schematic design so the terminal plan, wiring diagram and FAT procedure can be prepared correctly.

What tests are usually performed before delivery?

Common inspection and test items include visual inspection, dimension check, wiring continuity check, insulation resistance test, dielectric withstand test, main circuit connection check, secondary circuit function test, mechanical operation test, breaker operation check, metering and signal check, labeling check and nameplate check. For specific panels, ATS transfer logic, MCC control function and APFC step operation can also be tested.

What documents can be provided for project approval and handover?

Available documents can include technical datasheet, commercial quotation, GA drawing, internal layout drawing, foundation drawing, schematic diagram, control wiring diagram, terminal plan, cable entry drawing, BOM, component list, breaker list, CT list, metering list, compliance statement, technical deviation sheet, routine test report, FAT report, operation manual, maintenance manual, packing list, quality certificate and certificate of origin.

Get A Quote

Send Your LV Switchgear Requirements

Send your single-line diagram or a rough scope. Hank replies personally within 24 hours with a proposal, drawings and a clear next step.

Hank, your LV switchgear project contact

Hi, I'm Hank.

Your LV Switchgear Project Contact

Every message here reaches me directly, no bots, no junior reps. Send what you have and I come back with technical answers, not a brochure.

A single-line diagram or rough scope is enough to start. We've turned rough requirements into delivered LV switchgear for EPC contractors and project engineers across 45+ countries.

WhatsApp

+86 153 0640 9721

Reply Time

Within 24 Hours

Quote Request

Tell Us About Your Project

Fields marked are required.

Details stay private No sales spam Hank replies in person