20kV oil-immersed distribution transformer for industrial plant expansion
Quantity: 3 units
Outdoor transformer configuration with protection accessories, nameplates, routine test reports and project documents.
An oil-immersed transformer and medium voltage switchgear package supplied for an industrial plant expansion in Indonesia, covering system interface review, outdoor transformer configuration, MV feeder arrangement, testing documents and export shipment support.
An oil-immersed transformer and medium voltage switchgear package supplied for an industrial plant expansion in Indonesia, covering system interface review, outdoor transformer configuration, MV feeder arrangement, testing documents and export shipment support.
This project involved the supply of oil-immersed transformers and medium voltage switchgear for an industrial plant expansion in Indonesia. The equipment was used to support additional production capacity and improve the plant power distribution system.
Before production, the existing plant single-line diagram and new project specification were reviewed to confirm voltage ratio, transformer impedance, protection requirements, switchgear feeder arrangement, cable termination method and installation interface with the existing electrical system.
The equipment was manufactured, tested and prepared with the required drawings, test reports and shipment documents before delivery to the project site.
Send us your single line diagram and ratings. You get a matched proposal, drawings, and a delivery plan within 24 hours.
Every unit delivered for this project, with quantity and configuration notes.
Quantity: 3 units
Outdoor transformer configuration with protection accessories, nameplates, routine test reports and project documents.
Quantity: 1 lot
Including incoming panel, outgoing feeder panels, CT/PT arrangement, protection relay and metering configuration.
Tell us your voltage, capacity, and quantity. We confirm configuration, accessories, and lead time for your order.
Voltage, capacity, and protection parameters confirmed for this project.
| Parameter | Value | Notes |
|---|---|---|
| Transformer Capacity | 3150 kVA | Per transformer |
| Primary Voltage | 20 kV | Medium voltage side |
| Secondary Voltage | 0.4 kV | Low voltage side |
| Frequency | 50 Hz | Industrial plant system requirement |
| Vector Group | Dyn11 | Confirmed before production |
| Impedance | 6% | Matched to system short-circuit calculation |
| Cooling Method | ONAN | Outdoor oil natural air natural cooling |
| Installation | Outdoor | Industrial plant substation area |
| Transformer Protection | Buchholz relay, oil temperature indicator, winding temperature indicator | Accessory scope confirmed with customer |
| MV Switchgear Rated Voltage | 24 kV | Medium voltage switchgear system |
| MV Switchgear Rated Current | 1250 A | Main busbar rating |
| Short-circuit Current | 25 kA / 3s | According to project fault level requirement |
| Cable Entry | Bottom entry | Confirmed according to site cable trench layout |
Share your project specification and we map every parameter, vector group, and impedance to your requirement before production.
The requirement on site, and how the specification, drawings, and production were supported.
<p>The industrial plant expansion needed new transformer and MV switchgear equipment to connect with an existing power distribution system. The main technical concerns included voltage compatibility, transformer impedance, feeder arrangement, CT/PT selection, protection relay coordination, cable termination, outage planning and document approval before production.</p>
Our engineering team reviewed the existing system information, new project specification and single-line diagram before finalizing the proposal. Transformer ratings, impedance, protection accessories, MV switchgear arrangement, feeder schedule and metering requirements were checked against the plant electrical interface.
After the technical parameters were confirmed, we prepared drawings, datasheets, compliance documents, routine test reports and shipment documents to support project approval, installation and commissioning.
Our engineers review your drawings, deviations, and standards so your equipment clears consultant and utility approval the first time.
Inspection items and engineering documents prepared for this project.
<p>Routine tests were completed before shipment. Transformer testing included insulation resistance, voltage ratio, winding resistance, load loss, no-load loss, applied voltage and induced voltage. MV switchgear checks included mechanical operation, interlock function, secondary wiring inspection, insulation resistance and power frequency withstand voltage.</p>
We arrange routine tests, witness inspection, and full document sets so your equipment ships with proof of compliance.
Production, testing, and finished equipment from this project.
You get progress photos at production, testing, and packing stages so you track your order from factory to container.
Export packing, container loading, and nameplate records for this shipment.
Send your destination port and timeline. We handle export packing, loading, and documents so your equipment arrives ready to install.